The chart below lists the common nozzles used in testing fire pumps and their flow rating at set pressures. All nozzle pressures are pitot gauge readings, not pump pressure gauge readings. Flows are in U.S. gallons per minute. We have only shown the most popular tips sizes. If you have a tip that is not listed here, give us a call and we can get you the correct flow data for that tip. If the tip size you need is not in this chart, give us a call and we can look up the information you need. Or, if you skip to the bottom of this page, there is a formula you can use to find the answer you need.
D=Bore Diameter in Inches GPM=29.71D2*sqrt(NP) As we said, if you don't want to go through the hassle of calculating the flow, just give us a call and we will be more than happy to help. | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|